The Fike CV-S and CV-S-HV explosion vents have a pre-bulged composite construction. They’re use in applications where the operating pressures approach the burst pressure and where moderate to high vacuum pressure or cycling conditions may exist. Standard applications include separation, drying, preservation, transport, and processing operations.
Specification:
SPECIFICATION | ||
Type: | ROUND (CV-S) | RECTANGULAR (CV-S & CV-S-HV) |
Sizes: | Ø6” to Ø44” | 9” x 12” to 44” x 69” (CV-S)* |
Compliance: | NFPA 68, EN 14797, ATEX Certification available (consult factory) | |
Materials of Construction: | 316 SST / FEP or PFA / 316 SST | |
Maximum Operating Pressure: | 90% of the minimum stamped burst pressure for BP ≤ 1.5 psig (103 mbar) 80% of the minimum stamped burst pressure for BP > 1.5 psig (103 mbar) |
85% of minimum stamped burst pressure |
Standard Burst Pressure Tolerance: | ± 0.25 psig for burst pressures < 1.0 psig ± 0.5 psig for burst pressures 1.0 – 4.0 psig ± 1.0 psig for burst pressures > 4.0 psig |
|
Maximum Vacuum Rating: | Full vacuum (-14.7) for sizes up to 30” -7.35 psig for sizes > 30” |
Varies based on size and product type |
Burst Pressure Tolerance: |
± 0.25 psig for burst pressures < 1.0 psig (±17 mbar for BP < 69 mbar) ± 0.5 psig for burst pressures 1.0 – 4.0 psig (±34 mbar for BP 69 to 276 mbar) ± 1.0 psig for burst pressures > 4.0 psig (±69 mbar for BP >276 mbar) |
|
Operating Temperature Range: |
-40 to 400°F / -40 to 204°C (FEP) -40 to 500°F / -40 to 260°C (PFA) |
|
Optional Equipment: | Burst indicators / monitoring system; atmospheric insulation; process insulation; weather covers; frame assemblies; flameless venting; alternative materials, temperature ranges, and tighter tolerances are available |
Operating ratio | Temperature range | Vacuum resistant | Non-fragmenting | Pulsating / Cyclic |
80% | -40 – 260°C | ⇧⇧⇧ | • | ••⚬ |